Addressable Heat and Smoke Detector Combination Detector AW-D103
Product overview
Asenware AW-D103 is combined heat and smoke detector, it is an intelligent addressable detector, which can be configured with Asenware AW-FP100 Series Addressable Fire Alarm Control Panel. Each point (devices) can be given a specific ID, which allows the panel to continuously monitor a specific detector location (point). It reduces maintenance costs and makes it easier to maintain the system. It provides a fire signal when both conditions are satisfied which reduces the chances of false alarms. The heat sensing portion utilizes a proven thermistor for accurate and reliable heat detection.
Product Features
Addressable Heat and Smoke Detector Combination Detector Features:
- Addressable-analog communication
- Low standby current for continuous monitoring(≤2.5mA)
- Two-wire connection
- Two LEDs (RED), blinks in normal condition and becomes steady during fire alarm condition.
- Remote test from Panel
Spacing
Spacing of the detector must be followed by standard EN 54 or NFPA 72. NFPA 72 suggests for low airflow application spacing of 9.1 m for ceiling height up to 3.15 m can be applicable. However, please follow the specific codes and local codes for specific applications.